Test of control functions: At 3 s a restart file should be written At 5 s the fire should start DEVC for temperature should show rapid rise over 25 C but OBST should not disappear until 8 s is reached Case should die gracefully at 9 s &HEAD CHID='control_test', TITLE='Control function testing, SVN $Revision: 18027 $'/ &MESH XB=-1,1,-1,1,0,2, IJK=20,20,20 / &TIME T_END=10/ &SURF ID='FIRE', HRRPUA=1000. / &REAC SOOT_YIELD=0.01,FUEL='PROPANE'/ &OBST XB=-1,-0.5,-1,-0.5,1.5,2.0, CTRL_ID='all test', COLOR='CYAN' / &VENT MB='XMAX', SURF_ID='OPEN' / &VENT XB=-0.3,0.3,-0.3,0.3,0.0,0.0, COLOR='ORANGE', SURF_ID='FIRE', CTRL_ID='delay test' / &DEVC ID='timer1', QUANTITY='TIME', SETPOINT=9., XYZ=0,0,0 / &DEVC ID='timer2', QUANTITY='TIME', SETPOINT=3., XYZ=0,0,0 / &DEVC ID='timer3', QUANTITY='TIME', SETPOINT=8., XYZ=0,0,0 / &DEVC ID='temp', QUANTITY='TEMPERATURE', SETPOINT=25., XYZ=0,0,1.5 / &CTRL ID='kill test', FUNCTION_TYPE='KILL', INPUT_ID='timer1' / &CTRL ID='restart test',FUNCTION_TYPE='RESTART', INPUT_ID='timer2' / &CTRL ID='delay test', FUNCTION_TYPE='TIME_DELAY', INPUT_ID='timer2', DELAY=2. / &CTRL ID='all test', FUNCTION_TYPE='ALL', INPUT_ID='timer3','temp', INITIAL_STATE=.TRUE./ &TAIL /